First, the commissioning period failure
This type of fault occurs when the electromagnetic flowmeter is initially installed and debugged, but once it is improved, it will not appear again under the same conditions. Common failures during the commissioning period mainly include three reasons: improper installation, environmental interference, and fluid characteristics.
1, piping systems and installation aspects
Usually, the fault is caused by incorrect installation position of the electromagnetic flow sensor. For example, the flow sensor is installed at the high point of the pipe network which is easy to accumulate the retained gas; after the flow sensor, there is no back pressure, and the liquid is discharged straight into the atmosphere to form the inside of the measuring tube. Full pipe; installed on vertical pipes flowing from top to bottom, may appear empty.
2, the environmental aspects
Mainly due to pipeline stray current interference, space electromagnetic wave interference, large motor magnetic field interference. Pipe stray current interference usually takes good separate grounding protection to obtain satisfactory measurement, but if there is strong stray current in the pipeline (such as electrolysis workshop piping), it may not be overcome, and the flow sensor and pipeline must be taken (see below) Case 12). Space electromagnetic interference - usually transmitted through a signal cable, usually protected by a single layer or multiple layers of shielding, but it has also been overcome by shielding protection (see Case 10).
3, fluid aspects
The liquid containing uniformly distributed fine bubbles usually does not affect the normal measurement, but the measured volume flow is the sum of the liquid and the gas; the increase of the bubble causes the output signal to fluctuate, and if the bubble is large enough to flow through the electrode to cover the entire electrode surface, the electrode signal The loop is momentarily disconnected and the output signal will produce more fluctuations. Low-frequency (50/16 Hz-50/6 Hz) rectangular wave excitation electromagnetic flowmeter will produce slurry noise when the liquid contains more than a certain amount of solids, and the output signal will also fluctuate to some extent. When two or more liquids are used in the pipeline mixing process, if the conductivity of the two liquids (or the potential between the electrodes) is different, the flow sensor is measured before the mixing is not uniform, and the output signal also fluctuates. The electrode material and the measured medium are poorly matched, and chemical effects such as passivation or oxidation, formation of an insulating film on the surface of the electrode, and electrochemical and polarization phenomena may hinder normal measurement.
Second, the operating period failure
After the initial commissioning and normal operation for a period of time, the faults that occur during the operation are: the adhesion layer on the inner wall of the flow sensor, the lightning strike, and the environmental conditions.
1. Inner wall adhesion layer
Since the electromagnetic flowmeter measures much more than the other flow meters when measuring the suspended solid phase or the dirty body, the probability of failure of the inner wall adhesion layer is relatively high. If the conductivity of the adhesion layer is close to the liquid conductivity, the meter can output the signal normally, but only change the flow area to form a hidden fault of the measurement error; if it is a high conductivity adhesion layer, the electromotive force between the electrodes will be short-circuited; if it is an insulating adhesion layer The surface of the electrode is insulated to disconnect the measuring circuit. The latter two phenomena will make the meter inoperable.
2, lightning strike
Lightning strikes induce transient high voltages and surge currents in the line, and entering the meter can damage the meter. There are three ways to introduce the lightning damage meter: the power line, the flow signal line between the sensor spoon converter and the excitation line. However, from the analysis of damaged components in lightning faults, the induced high voltage and surge currents that cause faults are mostly introduced from the control room power line, and the other two approaches are less. It was also learned from the scene of the lightning strike that not only the electromagnetic flowmeter was faulty, but also other instrumentation in the control room often had lightning strikes at the same time. Therefore, the user must know the importance of setting up the lightning protection facilities of the control room instrument power cord.
3. Changes in environmental conditions
The main reason is the same as the fault environment in the commissioning period of the previous section, except that the interference source does not appear during the commissioning period and then intervenes during the operation. For example, an electromagnetic flowmeter with unsatisfactory grounding protection has normal operation due to no interference source during commissioning. However, new interference sources (such as pipelines near the measuring point or pipeline welding) interfere with the normal operation of the instrument during operation. , the output signal fluctuates greatly.
5.08MM Power+ Signal Power Connector
2.54MM Pitch Signal Power Connector.Chip power connector is used in power module system. It can select the matching power + signal connector according to the need. The feature is that the number of power and signal contacts and the matching sequence can be selected arbitrarily while keeping the connector size and contact core number unchanged.
Plug (male) / socket (female) can be installed at 90 or 180 degrees. It supports mixed or independent combination of signal and power. The quantity range of power and signal is (2-16) pin and (12-128) pin respectively
Product features
High temperature resistant, glass fiber reinforced and flame retardant polyester is used as insulation material
Copper gold composite conductor with high conductivity is used, and the contact area of the conductor is plated with gold
It adopts shrapnel contact, which has the characteristics of integration, small volume, large current carrying capacity, soft plug-in, blind plug-in, self guidance and high dynamic contact reliability. This series of products can be interchanged with FCI's powerblade series and Tyco's multi-beam series
The length of power hole / signal pin can be selected in two sizes. The power rated current is 45A and the signal rated current is 2.5A
5.08MM Power+ Signal Power Connector
ShenZhen Antenk Electronics Co,Ltd , https://www.antenkelec.com