First, the role of the weighing module
The signal of the on-site weighing sensor directly enters the PLC system instead of the ordinary weighing instrument sent to the PLC through the 4-20mA signal. Errors caused by signal conversion and time delays in transmission are avoided. The weighing control data has high real-time performance, and the speed of updating the weighing data is faster, and the control accuracy is higher.
Second, weighing module function overview
EM281-MWB/MWA is a dedicated weighing function module of OYES-200 series. It occupies the slot number after CPU (Note: can only be in slot number 0~2) and it occupies the address of 4AI/2AO. There is an RS485 electrical Interface, this interface supports Modbus protocol, through which the internal function parameters of EM281-MWB can be accessed to make the weighing more reliable and efficient; EM281-MWB/MWA can be cleared, preset tare weight, tare weight, and tare weight , Gross net weight switch, zero calibration, one calibration, two calibration, restore factory settings, save parameters to flash memory and other functions, provide special library function EM281_W_LIB_V2.0, making programming convenient, flexible application.
Third, function introduction
1. The wiring diagram of the on-site load cell and module is as follows (in kind shooting):
2. The RS485 communication port of EM281-MWB/MWA supports Modbus-RTU protocol. Through this communication port, the internal function parameters of the module can be set or other upper computer can obtain the weighing value through this communication port.
3. The application diagram of EM281-MWB/MWA is as follows: EM281 can only be in slot number 0~2, and up to 3 EM281 can be used simultaneously after CPU.

4, EM281-MWB use operating precautions a, in the use of program programming must be filtered in the system block analog input filter, as shown in Figure 4-1;
b. The configuration of a single channel should be completed one by one to avoid invalidation of the function setting.
c. The maximum range setting is reasonable; the maximum range is 10n of the maximum range of the sensor, n represents the decimal place when reading, for example, the sensor range is 20Kg, the maximum range is written to 200, then the read data is 1 decimal place,; the maximum range is written Enter 2000, the read data is 2 decimal places, the maximum range is written to 20000, then read data is 3 as decimal;
d, a calibration weight can not be less than 5% of the range, otherwise the calibration fails, and the calibration value is closer to 80% of the range, the better the calibration effect;
e. The difference between the weight of the secondary calibration weight and the one calibration weight cannot be less than 5% of the span, otherwise the calibration fails;
f. After the parameters are debugged in the Modbus communication, perform the “save parameter to flash†operation, or else re-commission after the next power up;
g, the provided library program only supports OYES EM281 series weighing module;
h. A maximum of 3 EM281 series weighing modules are supported after a single CPU;
i. The EM281 weighing module must be placed in the first 3 modules of the CPU to be used. Otherwise, Errors output 32767 or Control_Val output 32767;;
g, EM281 corresponding module number Em_No must be filled in correctly, that is placed in the CPU after the first module fill 0,
The second module fills 1, and the third module fills 2. It must be noted that otherwise the library program will not work properly.
Product use examples and more product information, please pay attention to the official number of Olympian public Otis technology, or log on the official website to download information.

AVS, AVSS, TXL, GXL, UL2464,UL1015,UL1007 normally used for car alarm wiring. JST, Dephi, Molex, and Chinese equipvalent part canbe assembly in the harness. Yacenter expands oversea markets, such as Europe, America,Janpan, etc. Owing to the rapid development, Yacenter has been awarded as [UL, CE, TS"certificate.
Any technical question, inquiry price, feel free to communicate with us.
Car Alarm Wiring,Car Alarm Wire Harness,Automobile Car Alarm Wire Harness,Car Stereo Alarm Wiring Harness
Dongguan YAC Electric Co,. LTD. , https://www.yacentercn.com